On 2025-05-10 9:46 a.m., Bill Sloman wrote:That is not unlike the failure in the UK Aug 2019 where an apparently inconsequential minor power station dropping off due to a lightning strike started a cascade failure that spread until they shed enough load to get a balance again. Wide area power cut resulted.One of my LinkedIn contacts - an IEEE contact in this case - posted some new data on LinkedIn, from a "Simon Gallagher, Managing Director at UK Networks Services | CEng | FIET | FEI | MBA "...
>
"We have had an update from ENTSO-E on the Spanish complete power failure. It is limited, but it helps to build the picture. I have updated our charts with the new information.
>
Updated timeline:
>
1. Large generators in the South of Spain started to trip at 12:32:57 CET. Over a period of 20 seconds a total of 2.2GW was lost – this is well beyond largest infeed so not secured against
>
2. The frequency looks to have been contained by system reserves until what looks like a large trip at 12:33:16
>
3. At this stage, the frequency falls at about 0.5 Hz/s for 4 seconds, until a rapid collapse starts
They are intrinsically dangerous if they store enough energy to really matter. We had such a steel reinforced lead flywheel and motor generator configuration on big radio telescopes storing just enough energy to stow them in the event of a storm taking out 3 phase mains power. The dishes can only reliably survive storms if they are pointed at the zenith."While I think a lack of inertia had an impact here, that does not mean that the level of solar and wind was to blame - rather it is how it has been integrated - more grid forming inverters, more rotating mass is needed, I suspect."Perhaps for systems that have large solar or wind arrays they could use a number of large rotating masses to smooth over these burps? Vacuum and magnetic bearings...
>
I imagine a series of rotating masses so if any single or several fail (earthquake, etc.) the system wouldn't collapse.Magnetic levitation vacuum pumps were all the rage when I was in Japan. That was until one day the entire world moved an inch to the left. Every last one of them crashed with shattered titanium blades everywhere and no vacuum/moist summer air in the chambers. Hell of a mess. After that we went back to conventional bearings in all earthquake countries.
As you say, there is little inertia in these solar systems unlike water or fuel generated power.The advantage of gas turbines or diesel generators is that when the rotor starts to slow it automatically increases the gas supply to try and maintain frequency. The stored energy in the rotor is significant but it it have the ability to output a bit extra or a bit less in response to changing load that makes them so handy for stability.